产品[
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器
]资料
如果您对该产品感兴趣的话,可以
产品名称:
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器
产品型号:
ThermoTrans A 20210
产品展商:
珠海仪器仪表网-珠海市伟民仪表有限公司
简单介绍
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器输入:热电阻PT100,PT1000,NI100.热电偶:J型,K型.输出:0 ... 20 mA,4 ... 20 mA,0 ... 5 V,0 ... 10 V.电源:24 V DC
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器的详细介绍
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器
输入:热电阻PT100,PT1000,NI100.热电偶:J型,K型.输出:0 ... 20 mA,4 ... 20 mA,0
... 5 V,0 ... 10 V.电源:24 V DC
| Input data
| Type of sensor
| Standard
| Measuring range
|
|
|
|
|
|
| Input
| Pt100
| DIN 60751
| -200 ... +850 °C
|
|
| Pt1000
| DIN 60751
| -200 ... +850 °C
|
|
| Ni100
| DIN 43760
| -60 ... +180 °C
|
|
|
|
| Connection
| 2-, 3- or 4-wire
(automatically recognized)
|
|
| signaled by a yellow LED
|
|
|
|
| Range of resistance incl. cable
resistance
| 0 ... 5 kohms
|
|
|
|
| Max. cable resistance
| 100 ohm
|
|
|
|
| Supply current
| 200 µA, 400 µA or 0 ... 500
µA
|
|
|
|
| Wire monitoring
| Open circuit detection
|
|
|
|
| Input error limits
| Resistance <5 kohms:
| ± (50 mohms + 0.05 % meas.
val.) for ranges > 15 ohms
|
|
| Resistance >5 kohms:
| ± (1 ohm + 0.05 % meas. val.)
for ranges > 50 ohms
|
|
|
|
| Input temperature coefficient
| <50 ppm/K of selected end
value
|
|
| (medium temperature
coefficient in the allowed temperature range, reference temperature
23 °C)
|
|
|
| Thermo couples
| |
| Input data
| Type of sensor
| Standard
| Measuring range
|
|
|
|
|
| Input
| Type J
| DIN 60584-1
| –210 … +1200 °C
|
|
| Type K
| DIN 60584-1
| –200 … +1372 °C
|
|
|
|
| Input resistance
| >10 Mohms
|
|
|
|
| Max. cable resistance
| 1 kohm
|
|
|
|
| Wire monitoring
| Open circuit detection
|
|
|
|
| Input error limits
| ± (10 µV + 0.05 % meas. val.)
for spans >2 mV
|
|
|
|
| Input temperature coefficient
| <50 ppm/K of selected end
value
|
|
| (medium temperature
coefficient in the allowed temperature range, reference temperature
23 °C)
|
|
|
|
| Cold junction compensation
| Internal (Pt100)
|
|
| external (Pt100), fixed value
or uncompensated
|
|
|
|
| Error of internal cold junction
compensation
| <1.5 K
|
|
|
|
| Error of external cold junction
compensation
| < 80 mohms + 0.1 % meas. val.
| by Pt100 for Tcomp= 0 ... 80
°C |
| Shunt voltages
|
|
|
|
| Input data
|
|
|
|
| Input
| -1000 ... 1000 mV
unipolar/bipolar
|
|
|
|
| Input resistance
| >10 Mohms
|
|
|
|
| Input error limits
| ± (200 µV + 0.05 % meas.
val.) for spans >50 mV
|
|
|
|
| Wire monitoring
| Open circuit detection
|
|
|
|
| Input temperature coefficient
| <50 ppm/K of selected end
value
|
|
| (medium temperature
coefficient in the allowed temperature range, reference temperature
23 °C)
|
|
|
|
| Overload
| 5 V across all inputs |
| Output data
|
|
|
|
| Outputs
| 0 ... 20 mA,
| calibrated switching
|
|
| 4 ... 20 mA,
| (default 4 ... 20 mA)
|
|
| 0 ... 5 V,
|
|
| 0 ... 10 V
|
|
|
|
| Control range
| 0 ... approx. 102.5 % span at
0 ... 20 mA, 0 ... 10V and 0 ... 5 V outputs
|
|
| -1.25 ... approx. 102.5 %
span at 4 ... 20 mA output
|
|
|
|
| Resolution
| 16 bit
|
|
|
|
|
| Load
| Current output:
| ≤10 V (≤500 ohms at 20 mA)
|
|
| Voltage output:
| ≤1 mA (≥10 kohms at 10 V)
|
|
|
|
|
| Output error limits
| Current output:
| ± (10 µA + 0.05 % meas. val.)
|
|
| Voltage output:
| ± (5 mV + 0.05 % meas. val.)
|
|
|
|
|
| Residual ripple
| <10 mVrms
|
|
|
|
| Output temperature coefficient
| <50 ppm/K of selected end
value
|
|
| (medium temperature
coefficient in the allowed temperature range, reference temperature
23 °C)
|
|
|
|
| Error signaling
| 0 ... 20 mA Output: I =0 mA
or ≥21 mA
|
|
| 4 ... 20 mA Output: I ≤3,6 mA
or ≥21 mA
|
|
| 0 ... 5 V and 0 ... 10 V
Output: V= 0 V or V≥5.25 V and V≥10.5 V respectively
|
|
| by output signal and red LED
for
|
|
| out-of-range conditions,
|
|
| incorrect parameter setting,
|
|
| sensor short-circuit and open
circuit
|
|
| output error load
|
|
| other device errors. See also
"Error signaling". |
| Transmission behavior
|
|
|
|
| Characteristic
| Linear rising / falling;
|
|
|
|
| Measuring rate
| Approx. 3 / s
*) |
| Display
|
|
|
|
| green LED
| Auxiliary power
|
|
|
|
| yellow LED
| Type of connection
|
|
|
|
| red LED
| Maintenance request or device
breakdown
|
|
|
| Power supply
|
|
|
|
| Power supply
| 24 V DC (-20 %, +25 %),
approx. 1.2 W
|
|
| Power supply can be routed
from one device to another via DIN rail bus-connectors. |
| Isolation
|
|
|
|
| Galvanic isolation
| 3-port isolation between
input, output, and power supply
|
|
|
|
| Test voltage
| 2,5 kV AC, 50 Hz: input
against output against power supply
|
|
|
|
| Working voltage
| Up to 300 V AC/DC across all
circuits at overvoltage category II and pollution degree 2 to EN
61010-1
|
| (basic insulation)
| For applications with high
working voltages, you should ensure there is sufficient spacing or
isolation from neighboring devices and protection against electric
shocks.
|
|
|
|
| Protection against electric
| Safe Isolation to EN 61140 by
reinforced insulation to EN 61010-1.
|
| shock
| Working voltage up to 300 V
AC/DC across all circuits at overvoltage category II and pollution
degree 2.
|
|
| For applications with high
working voltages, you should ensure there is sufficient spacing or
isolation from neighboring devices and protection against electric
shocks. |
| Standards and
approvals
|
|
|
|
| Explosion protection
| ATEX Zone 2 (EN 60079-15)
|
|
| Class 1, Div 2 / Zone 2 (UL
1604)
|
|
|
|
|
| EMC
| Product standard:
| EN 61326
|
|
| Emitted interference:
| Class B
|
|
| Immunity to interference 1):
| Industry
|
|
| EMC requirements for devices
with safety related functions IEC 61326-3
|
|
|
|
| cURus
| File No. 220033
|
|
| Standards: UL 508 and CAN/CSA
22.2 No. 14-95 |
| Other data
|
|
|
|
| Ambient temperature
| Operation:
| 0 ... +55 °C when placed
without spacing
|
|
|
| 0 ... +65 °C with spacings ≥
6 mm
|
|
| Transport and storage:
| -25 ... +85 °C
|
|
|
|
| Ambient conditions
| Stationary use, weatherproof
|
|
| Relative humidity: 5 ... 95
%, no condensation
|
|
| Air pressure: 70 ... 106 kPa
|
|
| Water or wind-driven
precipitation (rain, snow, hail etc.) excluded
|
|
|
|
| Design
| Modular housing with screw
terminals, 6.2 mm wide
|
|
| for further measurements and
mounting profile see "Dimension drawings"
|
|
|
|
| Protection class
| Terminals IP20, Housing IP40
|
|
|
|
| Mounting
| For 35 mm top-hat rail to EN
60715
|
|
|
|
| Weight
| Approx. 60 g
|
|
|
|
|
| *) For thermocouples with
external cold junction compensation: approx. 2 / s
|
| 1) Slight deviations are
possible while there is interference |
ThermoTrans A 20210 德国(KNICK)科尼克 温度变送器